500 PRO pH/ORP analog sensor

High performance industrial sensor for harsh applications

Placeholder
9PAA00000001714_master.jpg

Documentation

500 PRO | Analog pH/ORP sensor

Data Sheet

Specifications

Overview

Featuring a triple-junction design with ion traps, reference shielding and Viton® Extreme O-ring protection, the 500 PRO provides enhanced poisoning resistance and chemical protection, extending operational lifetime without compromising performance.

The 500 PRO sensor provides:

Increased efficiency

Propriety high performance glassware formulations provide the highest level of reliability and responsiveness
Close-coupled temperature measurement ensures high accuracy even with rapid temperature changes

Dependable performance

Triple junction design with ion-trap and reference shielding provides enhanced poisoning resistance
Unique tertiary cellular junction matrix slows poisoning effects, maximizing sensor lifetime
ATEX/IECEx certified for use in hazardous areas
Robust PVDF ¾ inch NPT body provides superior mechanical and chemical resistance
Each electrode is manufactured to the highest quality standards and provided with a calibration certificate

Modular design

Universal ¾ inch NPT design for simplified mounting
Available in a range of detached or integral cabling options

Data

Measurement range
pH 0 to 14 pH
Redox (ORP) –2000 to 2000 mV

Process temperature
–5 to 105 °C (23 to 221 °F)

Pressure range
0 to 10 bar (145 psi) @ 25 °C (77 °F)

Recommended minimum sample conductivity
50 μS/cm

pH glass
High performance (S) glass (bullet)
High performance (S) glass (flat)
Low temperature (LT) glass (bullet)
High temperature (HT) glass (bullet)
Hydrofluoric acid-resistant (HF) glass (bullet)

Redox (ORP)
Platinum
Reference system

Ag/AgCl with triple junction, KCl gel electrolyte plus ion trap

Reference junction
Porous PTFE and Viton® Extreme O-rings

Connection type
BNC + Molex
Tagged
VarioPin

Process connections
¾ inch NPT

Approvals, certification and safety

ATEX/IECEx
Certificate numbers: IECEx BAS 18.0047X
Bassefa18ATEX0071X

Entity parameters: Ui = 15.0 V
Ii = 20 mA
Ci = 5 NF
Li = 30 uH
CE Mark
Covers EMC+LV directives (including latest version of EN61010)

Regulation 31
Drinking water approval: Complies to DWI Regulation 31(4)(b)
Additional tests: BS6920 parts 2.2 and 2.4 on all wetted parts
EMC
Meets requirements of IEC61326 for an industrial environment
CRN Approval
Maximum allowable working pressure (MAWP): 5.58 bar (81 psi)
Design temperature: -5 ⁰C to + 105 ⁰C (+23 ⁰F to +221 ⁰F)
CRN number 0F22557 Certificate no. Sira MC220375/00
MCERTS
Certificate no. Sira MC220375/00

Benefits

Get in Touch

Need Help With A Product?

We work closely with a diverse network of manufacturers to bring you a wide range of instrumentation equipment options, ensuring that you find the perfect fit for your requirements.