HVT-FI Fabricated Insert Venturi / HVT-PI Plastic Insert Venturi
Documentation
Specifications
Overview
Data
Benefits
- Line Size
- 3 to 144 inches. Larger sizes available upon request.
- Head loss % of Differential
- 3.50 to 10.0 percent
- Basic Accuracy (% of Total)
- +/- 0.25 (Calibrated) +/- 0.50 (2 Sigma) (Uncalibrated)
- Minimum pipe Reynolds number
- Must be greater than 75,000 for basic accuracy
- Required Straight Piping
- Consult PFS datasheet
- Beta Range
- 0.20 through 0.80
- Useful Service Life
- Very Long
- Service Functional Limits
- Clear liquid, gas, and digester gas
- Applications
- Potable Water, Water Treatment Plant, Wastewater Treatment Plant, Air, Gas, Clean Liquids
- Common Materials
- Meter Type Body Throat
- FI (Fabricated Insert Venturi) 304SS or Carbon Steel 304 or 316SS
- PI (Plastic Insert Venturi) Fiberglass (FRP) 304 or 316SS
- Other Available Materials not limited to
- Aluminum, Zirconium, Hastelloy, Monel, Duplex SS, Titanium, Tantalum, 321SS
Get in Touch