Leakwise system consists of a controller and one or more sensors.
The ID-223 sensor has a high-frequency transmitter mounted on a float built in a guiding cage. The floating sensor maintains its position precisely at the liquid/air interface, despite fluctuations in liquid level. The ID-223 is controlled by the analog PS-220 Controller, which has two field-adjustable alarm points:
Low oil alarm – Detection of a first predefined layer thickness of hydrocarbons
High oil alarm – Detection of a hydrocarbon layer at a second predefined thickness or detecting a dry sump situation in certain applications.
The ID-223 can detect as little as 0.3 mm (0.01 in) oil on water reliably, repeatedly and without false alarms. It also monitors online changes in oil layer thickness up to 20 mm (0.8 in) and report it through a 4-20 mA output signal from the controller. Controller relays are used for local and remote alarms and control. Continuous built-in diagnostics monitor sensor operation. The SLC-220 digital controller handles up to four sensors. A stilling tube (available as an optional accessory) is recommended for ID-223 installations where lateral water velocity exceeds 30 cm/sec (11.8 in/sec).
Leakwise ID-223 has three sub-models for different maximum water fluctuation capabilities:
ID-223/500 – up to 500 mm (19.7 in)
ID-223/2000 – up to 2,000 mm (6.6 ft.) as standard, or up to newline
5,000 mm (16.4 ft.) on request
ID-223/2500 – up to 2,500 mm (8.2 ft.) as standard, or up to newline
5,500 mm (18 ft.) on request
Data
ID-223 Sensor Specifications
OPERATION
Summary: Floating sensor capable of monitoring hydrocarbons and other organic solvents on water and
in sumps that may be dry.
OPERATING RANGE
Detection Range: 0.3 – 20 mm (0.01 – 0.8 in) of hydrocarbon on water or brine
Water Level Variation: Depends on sensor sub-model – see below
Water Lateral Velocity: ~30 cm/sec (~11.8 in/sec) without a stiller; May be doubled with a stiller
Water Temperature: 0 – 70 °C (32 – 158 °F); no freezing
Air Temperature: -10 – 80 °C (14 – 176 °F)
PHYSICAL SPECIFICATIONS
Sub-Models:
ID-223/500
Floating Range: 40 – 500 mm (1.6 – 19.7 in) – Guiding Cage Dia.: 180 mm (7.1 in)
ID-223/2000
Floating Range: 70 – 2000 mm (2.8 – 78.7 in) – Guiding Cage Dia.: 560 mm (22.1 in)
ID-223/2500
Floating Range: 70 – 2500 mm (2.8 – 98.4 in) – Guiding Cage Dia.: 280 mm (11.0 in)
Sensor:
Materials: Hydrocarbon resistant polymers, 316 stainless steel.
Diameter: 87 mm (3.4 in).
Integral Cable: 10 m (~33 ft.) supplied with sensor, 3 x 18 AWG, blue PVC jacket.
Accessories: Integral stiller for each sub-model; Anti-Submersion air pocket for ID-223/500 and
ID-223/2500
PS-220 Controller Specifications and Options
SPECIFICATIONS
PS-220 Description: PS-220 Controller is an analog signal processor and power supply in a
NEMA 4 enclosure and supports a single ID-223 sensor.
Temperature: Ambient temperature range: -40 – 85 °C (-40 – 185 °F)
Cable length to Sensor Up to 1,200 m (3,937 ft.) subject to hazardous area restrictions.
PS-220/RL/LI Two alarm relays with dry contacts and one fail relay contact: SPDT rated 4A (3A for fail
contact) at 250 VAC or 30 VDC, normally open and normally closed, and four status indication lights: Water, Oil, Air/High Oil and Fail. Includes built-in diagnostics.
Wiring Connections Terminal blocks: 14 AWG maximum for sensor and 4-20 mA output wires; 12 AWG
maximum for power and relays wires.
OPTIONS
Enclosure Options:
-N4 for NEMA 4X (IP65): 305 x 195 x 120 mm (12.0 x 7.7 x 4.7 in) 2 Kg (4.4 lb.);
-N7 for NEMA 7: 278 x 259 x 166 mm (11.0 x 10.2 x 6.5 in) 8.5 Kg (18.7 lb.);
-Exd for Ex d: 355 x 276 x 200 mm (14.0 x 10.9 x 7.9 in), 14 Kg (30.9 lb.);
-BP: without an enclosure, to be mounted in a local cabinet. 190 x 180 x 130 mm, 1 Kg.
Input Power Options 220 or 110 VAC (50 – 60 Hz) or 9 – 36 VDC (@ 5 Watts); may also be solar powered.
-420 4-20 mA analog output proportional to hydrocarbon thickness up to 25 mm (1.0 in), current source.
-420/BG Bar-Graph display (20 bars) of hydrocarbon thickness in addition to 4-20 mA analog output.
-CEN Zener Safety Barriers to allow installation of the sensor in hazardous areas.
-AUD Audio alarm option (available in weather-proof or explosion-proof enclosure
Benefits
Get in Touch
Need Help With A Product?
We work closely with a diverse network of manufacturers to bring you a wide range of instrumentation equipment options, ensuring that you find the perfect fit for your requirements.