Laser level transmitter LLT100

Non-contact, level measuring instrument designed for industrial applications and harsh environments

Placeholder
9IBA210907_400x400.jpg

Documentation

Level Product Overview | Measurement made easy

Product Brochure

Specifications

Overview

The LLT100 is specifically made for industrial applications and harsh environments. It provides continuous, non-contact level measurement capabilities for process automation and inventory management in industries such as mining, aggregates, oil and gas, chemicals, food and beverages, power, pulp and paper, pharma, and water and waste water.

Low cost of ownership
– No maintenance
– No calibration necessary
– Versatile level transmitter

Reliable
– Precise measurement of any solid or liquid surface
– Dust and fog penetration capabilities
– Explosion proof class 1 / division 1 (zone 1)

Convenient
– Fast and flexible installation
– Easy setup function
– 2 wire powered and HART communication

Accessories

Dust tube
– Avoids dirt or splashing liquids on the window

Cooling tube
– Increases max. process temperature to 280°C/535°F

Heated window
– Prevents condensation on window (requires 4 wire power)

Integral Through-the-Glass user interface
– Configuration directly on the unit

Rotating bracket
– Ideal for aiming the LLT100 laser beam

Swivel flange
– Provides precise aiming of the LLT100 laser beam. Especially useful in liquid applications

Laser pointer tool
– Used to provide a visual reference when aligning LLT100

Process flanges

Universal flange (aluminum or stainless steel)
– Flange bolt pattern fits both 2 in. ASME150 and DN50 PN 16
– Maximum pressure: 2 bar (29 psi)
– Hazarous area class 1 / division 1 (zone 1)

High pressure
– 2 in. class 150 flange
– 2 in. class 300 flange
– DN50 PN16 flange
– DN50 PN40 flange
– Hazardous area class 1 / division 1 (zone 1)
– Can be used to form a barrier to zone 0

Hygienic interface
– 4 in. triclover clamp

Data

Measurement

Range
0.5 to 30 m (2 to 100 ft) for liquids
0.5 to 100 m (2 to 330 ft) for solids
0.5 m to 200 m (2 ft to 660 ft) for positioning applications with reflective target

Resolution
5 mm (0.2 in)

Typical accuracy
±11 mm (0.4 in)

Measuring beam
Laser wave length: 905 nm, eye safe, Class 1

Laser beam divergence
< 0.35°

Environmental conditions

Operating temperature
–40° to +60°C (–40 to +140°F), up to 280°C (535°F) with cooling tube

Storage temperature
–40 to +85°C (-40 to +185°F)

Survival temperature
–40°C to +80°C (–40°F to +175°F)

Process pressure
– Base model: –1 to +2 bar (29 psi)
– Hygienic model: –1 to +1 bar (15 psi)
– Pressure-rated model: –1 to +49.6 bar (719 psi), depending on flange

Output

Analog
4 to 20 mA, NAMUR compliant
Digital
HART 7 (multi-variable output)
Communication
Local HMI, EDD/DTM, handheld

Power supply

Powered from the loop
4 to 20 mA, 16 to 42 V DC
Heated lens option
24 V DC (3W)

Mechanical

Enclosure material
Powder coated aluminum (standard), 316L stainless steel (option)
Dimensions
– Universal – flat flange W 247 x H 215 x D 165 mm (9.7 x 8.5 x 6.5 in.)
– Class 150 – raised flange W 240 x H 242 x D 154 mm (9.5 x 9.5 x 6.1 in.)
– Class 300 – raised flange W 247 x H 242 x D 165 mm (9.7 x 9.5 x 6.5 in.)
– DIN PN 16 – raised flange W 247 x H 242 x D 165 mm (9.7 in x 9.5 x 6.5 in.)
– DIN PN 40 – raised flange W 247 x H 242 mm x D 165 (9.7 x 9.5 x 6.5 in.)
– Hygienic flange W 223 x H 215 x D 137 mm (8.8 x 8.5 x 5.4 in.)
Weight of standard model
– Aluminum enclosure with universal aluminum flange: 3.7 kg (8.2 lb)
– 316L SST enclosure with universal stainless steel flange: 8.6 kg (19.0 lb)
Weight of pressure rated model
– Aluminum enclosure: 6.7 to 7.2 kg (14.8 to 15.9 lb), depending on flange
– 316L SST enclosure: 10.0 to 10.5 kg (22.1 to 23.2 lb), depending on flange
Weight of hygienic model
– Aluminum enclosure: 5.8 kg (12.8 lb)
– 316L SST enclosure: 9.1 kg (20.1 lb)
Protection class
IP66 / IP67/ Nema 4 (SS version 4X)
Process fitting
– Flange (ASME 2”, DN50)
– Hygienic fitting / tri-clamp 4 in. (ISO2852)
Wetted parts
– Aluminum, cemented borosilicate window (base model)
– 316L SST, cemented borosilicate window (base model, hygienic model)
– 316L SST, fused borosilicate window (high pressure models)

Operation

Display
– Integrated 128×64 pixels LCD display with TTG (Through-The-Glass) interface
Software features
– Volume computation, damping, filtering, thresholds/alarms, user-defined display(with HMI)
Approvals CE, ATEX, IECEx, FM, 3A

Benefits

Get in Touch

Need Help With A Product?

We work closely with a diverse network of manufacturers to bring you a wide range of instrumentation equipment options, ensuring that you find the perfect fit for your requirements.