PS-220 Analog Controller

Placeholder
PS20N420Water20M200001-1.jpg

Documentation

PS-220 ANALOG CONTROLLER

Data Sheet

Specifications

Overview

PS-220 Analog Leakwise Controller is a power supply and signal processor that interfaces with a single Leakwise ID-220 Series Sensor to report hydrocarbons spill/leak alerts, including layer buildup and thickness, to users via outputs for local or remote reporting. PS-220 has well-proven reliability and is cost-effective for a basic monitoring system. It can be AC or DC line powered.

Data

PS-220 Controller Specifications and Options

Specifications

PS-220 Controller is an analog signal processor and power supply in a NEMA 4 enclosure, and supports a single ID-220 Series Leakwise sensor

Temperature: Ambient temperature range: -40 – 85 °C (-40 – 185 °F)

Cable length to Sensor: Up to 1,200 m (3,937 ft.) subject to hazardous area restrictions.

PS-220/RL/LI: Two alarm relays with dry contacts and one fail relay contact: SPDT rated 4A (3A for fail

contact) at 250 VAC or 30 VDC, normally open and normally closed, and four status indication lights: Water, Oil, Air / High Oil and Fail. Includes built-in diagnostics.

Wiring Connections: Terminal blocks: 14 AWG maximum for sensor and 4-20 mA output wires; 12 AWG

maximum for power and relays wires.

OPTIONS

Enclosure Options:

-N4 for NEMA 4X (IP65): 305 x 195 x 120 mm (12.0 x 7.7 x 4.7 in) 2 Kg (4.4 lb.);

-N7 for NEMA 7: 278 x 259 x 166 mm (11.0 x 10.2 x 6.5 in) 8.5 Kg (18.7 lb.);

-Exd for Ex d: 355 x 276 x 200 mm (14.0 x 10.9 x 7.9 in), 14 Kg (30.9 lb.);

-BP: without an enclosure, to be mounted in a local cabinet. 190 x 180 x 130 mm, 1 Kg.

Input Power Options 220 or 110 VAC (50 – 60 Hz) or 9 – 36 VDC (@ 5 Watts); may also be solar powered.

-420 4-20 mA analog output proportional to hydrocarbon thickness up to 25 mm (1.0 in), current source.

-420/BG Bar-Graph display (20 bars) of hydrocarbon thickness in addition to 4-20 mA analog output.

-CEN Zener Safety Barriers to allow installation of the sensor in hazardous areas.

-AUD Audio alarm option (available in weather-proof or explosion-proof enclosure

Other Controllers – Refer to separate data sheets

SLC-220: Digital Signal Processor for up to four ID-220 Series sensors support, with various output options, including relays, lights, 4-20 mA, LCD, Modbus in RS-232 and RS-485 communication, and remote cellular connectivity. Controllers – Refer to separate data sheets

PS-220 Controller Certifications

For hazardous areas:

North America – NEMA 7, Class I, Div 1, Groups B, C & D; NEMA 4

Europe ATEX & IECEx – II2(1)GD, Ex db [ia Ga] IIC T6 Gb IP66

Combined System: Approved for operation in hazardous locations when Zener Safety Barriers are added

Manufacturing ISO 9001:2015 Certified

Benefits

Get in Touch

Need Help With A Product?

We work closely with a diverse network of manufacturers to bring you a wide range of instrumentation equipment options, ensuring that you find the perfect fit for your requirements.